7 Finishing the outdoor unit installation
Installation manual
13
ERRA08~12E
Daikin Altherma 3 R MT
4P708481-1 – 2023.02
6.5 To reposition the air thermistor on
the outdoor unit
This procedure is only necessary in areas with low ambient
temperatures.
Required accessory (delivered with the unit):
Thermistor fixture.
2 3
Click
4 5
6
7
7 Finishing the outdoor unit
installation
7.1 Insulate and fix the refrigerant
piping and cable
1 Insulate and fix the refrigerant piping and cables as follows:
g
b
a
f
e
cd
a Gas pipe
b Gas pipe insulation
c Interconnection cable
d Field wiring (if applicable)
e Liquid pipe
f Liquid pipe insulation
g Finishing tape
2 Install the service cover.
7.2 To close the outdoor unit
NOTICE
When closing the outdoor unit cover, make sure that the
tightening torque does NOT exceed 4.1N•m.
1 If necessary, close the side cover.
1
8×
3
3
3
7×
2
2
2 Close the service cover.