9.9.8 [5-09] R/W 0~20 kW, step: 0,5 kW
20 kW
9.9.9 [5-09] R/W 0~20 kW, step: 0,5 kW
20 kW
9.9.A [5-0A] R/W 0~20 kW, step: 0,5 kW
20 kW
9.9.B [5-0B] R/W 0~20 kW, step: 0,5 kW
20 kW
9.9.C [5-0C] R/W 0~20 kW, step: 0,5 kW
20 kW
9.9.D [4-01]
0: None
1: BSH
2: BUH
└─ Energy metering
9.A.1 [D-08] R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000
closed
9.E [3-00] R/W 0: No
1: Yes
9.F [E-08] R/O
0: disabled
1: Enabled
9.G R/W 0: No
1: Yes
└─ Overview field settings
9.I [0-00] R/W [9-05]~min(45,[9-06])°C, step: 1°C
35°C
9.I [0-01] R/W [9-05]~[9-06]°C, step: 1°C
50°C
9.I [0-02] R/W 10~25°C, step: 1°C
15°C
9.I [0-03] R/W -40~5°C, step: 1°C
-10°C
9.I [0-04] R/W [9-07]~[9-08]°C, step: 1°C
8°C
9.I [0-05] R/W [9-07]~[9-08]°C, step: 1°C
12°C
9.I [0-06] R/W 25~43°C, step: 1°C
35°C
9.I [0-07] R/W 10~25°C, step: 1°C
20°C
9.I [0-0B] R/W 35~[6-0E]°C, step: 1°C
55°C
9.I [0-0C] R/W 45~[6-0E]°C, step: 1°C
60°C
9.I [0-0D] R/W 10~25°C, step: 1°C
15°C
9.I [0-0E] R/W -40~5°C, step: 1°C
-10°C
9.I [1-00] R/W -40~5°C, step: 1°C
-10°C
9.I [1-01] R/W 10~25°C, step: 1°C
15°C
9.I [1-02] R/W
[9-01]~[9-00], step: 1°C
35°C
9.I [1-03] R/W [9-01]~min(45, [9-00])°C , step: 1°C
25°C
9.I [1-04] R/W 0: Disabled
1: Enabled
9.I [1-05] R/W 0: Disabled
1: Enabled
9.I [1-06] R/W 10~25°C, step: 1°C
20°C
9.I [1-07] R/W
25~43°C, step: 1°C
35°C
Limit 3
Limit 4
Limit
Limit 1
Limit 2
Limit 3
Limit 4
Priority heater
Electricity meter 1
Electricity meter 2
External sensor
Ext. amb. sensor offset
Averaging time
Bivalent
Boiler efficiency
Temperature
Hysteresis
Alarm output
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
Weather dependent cooling of the main leaving water temperature zone.
Weather dependent cooling of the additional leaving water temperature zone
Low ambient temp. for LWT main zone heating WD curve.
High ambient temp. for LWT main zone heating WD curve.
High ambient temp. for LWT main z
one cooling WD curve.
Auto restart
Power saving function
Disable protections
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
High ambient temp. for LWT add zone cooling WD curve.
Low ambient temp. for LWT add zone cooling WD curve.
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
High ambient temp. for LWT add zone heating WD curve.
Low ambient temp. for LWT add zone heating WD curve.
Leaving water value for high ambient temp. for LWT add zone cooling WD curve.
Leaving water value for low ambient temp. for LWT add zone cooling WD curve.
Low ambient temp. for LWT main zone cooling WD curve.
Leaving water value for high ambient temp. for DHW WD curve.
Leaving water value for low ambient temp. for DHW WD curve.
High ambient temp. for DHW WD curve.
Low ambient temp. for DHW WD curve.
4P556072-1 - 2018.12 (#) Setting is not applicable for this unit.
(*1) *6V_(*2) *9W_
(*3) *AB*_(*4) EAV*_
(*5) *X*_(*6) *H*_
(*7) EAV*18*_(*8) EAV*23*