5 Configuration
Installation manual
17
EBLQ+EDLQ011~016CA3V3+W1
Daikin Altherma low temperature monobloc
4P537990-1 – 2018.05
# Code Description
[A.2.2.F.3] [D-08] Optional external kWh meter1:
0 (No): NOT installed
1: Installed (0.1pulse/kWh)
2: Installed (1pulse/kWh)
3: Installed (10pulse/kWh)
4: Installed (100pulse/kWh)
5: Installed (1000pulse/kWh)
[A.2.2.F.4] [D-09] Optional external kWh meter2:
0 (No): NOT installed
1: Installed (0.1pulse/kWh)
2: Installed (1pulse/kWh)
3: Installed (10pulse/kWh)
4: Installed (100pulse/kWh)
5: Installed (1000pulse/kWh)
# Code Description
[A.2.2.F.5] [C-08] External sensor (indoor):
0 (No): NOT installed.
1 (Outdoor sensor): Remote outdoor
sensor, connected to the outdoor
unit.
2 (Room sensor): Remote indoor
sensor, connected to option box
EK2CB07CAV3.
INFORMATION
You can only connect either the remote indoor sensor or
the remote outdoor sensor.
# Code Description
[A.2.2.F.6] [D-04] PCC by digital inputs:
0 (No)
1 (Yes)
5.2.4 Quick wizard: Capacities (energy
metering)
# Code Description
[A.2.3.1] [6-02] Booster heater capacity [kW]
[A.2.3.2] [6-03] Backup heater capacity (step 1) [kW]
5.2.5 Space heating/cooling control
Leaving water temperature: Main zone
# Code Description
[A.3.1.1.1] N/A Setpoint mode:
0 (Fixed): Absolute
1 (Weather dep.): Weather-
dependent
2 (Fixed/scheduled): Absolute +
scheduled (only for leaving water
temperature control)
3 (WD/scheduled): Weather-
dependent + scheduled (only for
leaving water temperature control)
# Code Description
[7.7.1.1] [1-00]
[1-01]
[1-02]
[1-03]
Weather-dependent curve (heating):
[1-03]
[1-02]
T
a
T
t
[1-00] [1-01]
T
t
: Target leaving water temperature
(main)
T
a
: Outdoor temperature
[7.7.1.2] [1-06]
[1-07]
[1‑08]
[1-09]
Weather-dependent curve (cooling):
[1-09]
[1-08]
T
a
T
t
[1-06] [1-07]
T
t
: Target leaving water temperature
(main)
T
a
: Outdoor temperature
Leaving water temperature: Additional zone
# Code Description
[A.3.1.2.1] N/A Setpoint mode:
0 (Fixed): Absolute
1 (Weather dep.): Weather-
dependent
2 (Fixed/scheduled): Absolute +
scheduled (only for leaving water
temperature control)
3 (WD/scheduled): Weather-
dependent + scheduled (only for
leaving water temperature control)
[7.7.2.1] [0-00]
[0-01]
[0-02]
[0-03]
Weather-dependent curve (heating):
[0-00]
[0-01]
T
a
T
t
[0-03] [0-02]
T
t
: Target leaving water temperature
(additional)
T
a
: Outdoor temperature