7.2.4 Space heating/cooling control
Leaving water temperature: Main zone
# Code Description
[A.3.1.1.1] N/A Select the setpoint mode of the leaving
water temperature.
LWT setpoint mode:
▪ 0 (Fixed): Absolute
▪ 1 (Weather dep.): Weather-
dependent
▪ 2 (Fixed/scheduled): Absolute +
scheduled (only if Unit control
method=LWT control)
▪ 3 (WD/scheduled): Weather-
dependent + scheduled (only if Unit
control method=LWT control)
[7.7.1.1] [1-00]
[1-01]
[1-02]
[1-03]
If you selected weather-dependent
curve as a setpoint mode, adjust the
curve to your needs.
(a)
Set weather-dependent heating:
[1-03]
[1-02]
T
a
T
t
[1-00] [1-01]
▪ T
t
: Target leaving water temperature
(main)
▪ T
a
: Outdoor temperature
[7.7.1.2] [1-06]
[1-07]
[1‑08]
[1-09]
If you selected weather-dependent
curve as a setpoint mode, adjust the
curve to your needs.
(a)
Set weather-dependent cooling:
[1-09]
[1-08]
T
a
T
t
[1-06] [1-07]
▪ T
t
: Target leaving water temperature
(main)
▪ T
a
: Outdoor temperature
(a)
Also see "7.3Weather-dependent curve"[422].
Leaving water temperature: Additional zone
# Code Description
[A.3.1.2.1] N/A Select the setpoint mode of the leaving
water temperature.
LWT setpoint mode:
▪ 0 (Fixed): Absolute
▪ 1 (Weather dep.): Weather-
dependent
▪ 2 (Fixed/scheduled): Absolute +
scheduled (only if Unit control
method=LWT control)
▪ 3 (WD/scheduled): Weather-
dependent + scheduled (only if Unit
control method=LWT control)
[7.7.2.1] [0-00]
[0-01]
[0-02]
[0-03]
If you selected weather-dependent
curve as a setpoint mode, adjust the
curve to your needs.
(a)
Set weather-dependent heating:
[0-00]
[0-01]
T
a
T
t
[0-03] [0-02]
▪ T
t
: Target leaving water temperature
(additional)
▪ T
a
: Outdoor temperature
[7.7.2.2] [0-04]
[0-05]
[0-06]
[0-07]
If you selected weather-dependent
curve as a setpoint mode, adjust the
curve to your needs.
(a)
Set weather-dependent cooling:
[0-04]
[0-05]
T
a
T
t
[0-07] [0-06]
▪ T
t
: Target leaving water temperature
(additional)
▪ T
a
: Outdoor temperature
(a)
Also see "7.3Weather-dependent curve"[422].
Leaving water temperature: Delta T source
The Delta T is the required temperature difference between entering
and leaving water. This applies to both temperature zones. Change
the value of Delta T if another minimum temperature difference is
required for the good operation of the heat emitters in heating or
cooling mode.
# Code Description
[A.3.1.3.1] [1-0B] Delta T for heating
Range: 3°C~10°C
[A.3.1.3.2] [1-0D] Delta T for cooling
Range: 3°C~10°C