14 Technical data
Installer reference guide
101
ERLQ004~008CA + EHVH/X04+08S18+26CB
Daikin Altherma – Low temperature split
4P384973-1A – 2016.02
14.7 Technical specifications
14.7.1 Technical specifications: Outdoor unit
Nominal capacity and nominal input
Heating only type Reversible type
Outdoor units ERLQ004CAV
3
ERLQ006CAV
3
ERLQ008CAV
3
ERLQ004CAV
3
ERLQ006CAV
3
ERLQ008CAV
3
Indoor units EHBH04 EHBH08 EHBX04 EHBX08
EHVH04 EHVH08 EHVX04 EHVX08
Condition 1
(a)
Heating capacity Minimum 1.80kW
Nominal 4.40kW 6.00kW 7.40kW 4.40kW 6.00kW 7.40kW
Maximum 5.12kW 8.35kW 10.02kW 5.12kW 8.35kW 10.02kW
Cooling capacity Minimum — 2.00kW 2.50kW
Nominal — 5.00kW 6.76kW 6.86kW
Maximum —
Heating PI Nominal 0.87kW 1.27kW 1.66kW 0.87kW 1.27kW 1.66kW
Cooling PI Nominal — 1.48kW 1.96kW 2.01kW
COP Nominal 5.04 4.74 4.45 5.04 4.74 4.45
EER Nominal — 3.37 3.45 3.42
Condition 2
(b)
Heating capacity Minimum 1.80kW
Nominal 4.03kW 5.67kW 6.89kW 4.03kW 5.67kW 6.89kW
Maximum 4.90kW 7.95kW 9.53kW 4.90kW 7.95kW 9.53kW
Cooling capacity Minimum — 2.00kW 2.50kW
Nominal — 4.17kW 4.84kW 5.36kW
Maximum —
Heating PI Nominal 1.13kW 1.59kW 2.01kW 1.13kW 1.59kW 2.01kW
Cooling PI Nominal — 1.80kW 2.07kW 2.34kW
COP Nominal 3.58 3.56 3.42 3.58 3.56 3.42
EER Nominal — 2.32 2.34 2.29
(a) In heating: Ambient temperature DB/WB 7°C/6°C – leaving water condenser 35°C (DT=5°C). In cooling: Ambient temperature 35°C – leaving
water evaporator 18°C (DT=5°C)
(b) In heating: Ambient temperature DB/WB 7°C/6°C – leaving water condenser 45°C (DT=5°C). In cooling: Ambient temperature 35°C – leaving
water evaporator 7°C (DT=5°C)
Technical specifications
Outdoor units ERLQ004CAV3 ERLQ006CAV3 ERLQ008CAV3
Casing
Colour Ivory white
Material Polyester painted galvanised steel
Dimensions
Packing (H×W×D) 797×990×390mm
Unit (H×W×D) 735×832×307mm
Weight
Machine weight 54kg 56kg
Gross weight 57kg 59kg
Packing
Material EPS, carton
Weight 3kg
Heat exchanger