5 Application guidelines
Installer reference guide
12
ERLQ004~008CA + EHVH/X04+08S18+26CB
Daikin Altherma – Low temperature split
4P384973-1A – 2016.02
Underfloor heating or radiators – Wireless room
thermostat
Setup
B
A
b
a
A Main leaving water temperature zone
B One single room
a Receiver for wireless external room thermostat
b Wireless external room thermostat
The underfloor heating or radiators are directly connected to the
indoor unit.
The room temperature is controlled by the wireless external room
thermostat (optional equipment EKRTR1).
Configuration
Setting Value
Unit temperature control:
#: [A.2.1.7]
Code: [C-07]
1 (Ext RT control): Unit operation
is decided by the external
thermostat.
Number of water temperature
zones:
#: [A.2.1.8]
Code: [7-02]
0 (1 LWT zone): Main
External room thermostat for the
main zone:
#: [A.2.2.4]
Code: [C-05]
1 (Thermo ON/OFF): When the
used external room thermostat or
heatpump convector can only
send a thermo ON/OFF
condition.
Benefits
Wireless. The Daikin external room thermostat is available in a
wireless version.
Efficiency. Although the external room thermostat only sends ON/
OFF signals, it is specifically designed for the heatpump system.
Comfort. In case of under floor heating, the wireless external
room thermostat prevents condensation on the floor during cooling
operation by measuring the room humidity.
Heatpump convectors
Setup
B
A
a
A Main leaving water temperature zone
B One single room
a Remote controller of the heatpump convectors
The underfloor heating or radiators are directly connected to the
indoor unit.
The desired room temperature is set via the remote controller of
the heatpump convectors.
The space heating/cooling demand signal is sent to one digital
input on the indoor unit (X2M/1 and X2M/4).
The space operation mode is sent to the heatpump convectors by
one digital output on the indoor unit (X2M/32 and X2M/33).
INFORMATION
When using multiple heat pump convectors, make sure
each one receives the infrared signal from the remote
controller of the heatpump convectors.
Configuration
Setting Value
Unit temperature control:
#: [A.2.1.7]
Code: [C-07]
1 (Ext RT control): Unit operation
is decided by the external
thermostat.
Number of water temperature
zones:
#: [A.2.1.8]
Code: [7-02]
0 (1 LWT zone): Main
External room thermostat for the
main zone:
#: [A.2.2.4]
Code: [C-05]
1 (Thermo ON/OFF): When the
used external room thermostat or
heatpump convector can only
send a thermo ON/OFF
condition. No separation between
heating or cooling demand.
Benefits
Cooling. The heat pump convector offers, besides heating
capacity, also excellent cooling capacity.
Efficiency. Optimal energy efficiency because of the interlink
function.
Stylish.
Combination: Underfloor heating + Heatpump
convectors
Space heating is provided by:
The underfloor heating
The heatpump convectors
Space cooling is provided by the heatpump convectors only. The
underfloor heating is shut off by the shut-off valve.
Setup
B
A
a
M1
A Main leaving water temperature zone
B One single room
a Remote controller of the heatpump convectors
The heat pump convectors are directly connected to the indoor
unit.