8 Configuration
Installer reference guide
54
ERLQ004~008CA + EHVH/X04+08S18+26CB
Daikin Altherma – Low temperature split
4P384973-1A – 2016.02
# Code Description
[7.7.1.2] [1-06]
[1-07]
[1‑08]
[1-09]
<< continuation
[1-06]: Low outdoor ambient
temperature. 10°C~25°C (default:
20°C)
[1-07]: High outdoor ambient
temperature. 25°C~43°C (default:
35°C)
[1-08]: Desired leaving water
temperature when the outdoor
temperature equals or drops below
the low ambient temperature.
[9‑03]°C~[9‑02]°C (default: 22°C).
Note: This value should be higher
than [1-09] as for low outdoor
temperatures less cold water
suffices.
[1-09]: Desired leaving water
temperature when the outdoor
temperature equals or rises above
the high ambient temperature.
[9‑03]°C~[9‑02]°C (default: 18°C).
Note: This value should be lower
than [1-08] as for high outdoor
temperatures colder water is
required.
Leaving water temperature: Additional zone
Only applicable if 2 leaving water temperature zones are present.
# Code Description
[A.3.1.2.1] N/A LWT setpoint mode:
Fixed (default): The desired leaving
water temperature is:
NOT weather-dependent (i.e. does
NOT depend on the outdoor
ambient temperature)
fixed in time (i.e., NOT scheduled)
Weather dep.: The desired leaving
water temperature is:
weather-dependent (i.e. depends
on the outdoor ambient
temperature)
fixed in time (i.e., NOT scheduled)
Fixed/scheduled: The desired leaving
water temperature is:
NOT weather-dependent (i.e.,
does NOT depend on the outdoor
ambient temperature)
according a schedule. The
scheduled actions are On or OFF.
Remark: This value can only be
set in leaving water temperature
control.
WD/scheduled: The desired leaving
water temperature is:
weather-dependent (i.e., does
depend on the outdoor ambient
temperature)
according a schedule. The
scheduled actions are On or OFF.
Remark: This value can only be
set in leaving water temperature
control.
# Code Description
[7.7.2.1] [0-00]
[0-01]
[0-02]
[0-03]
Set weather-dependent heating:
[0-00]
[0-01]
T
a
T
t
[0-03] [0-02]
T
t
: Target leaving water temperature
(additional)
T
a
: Outdoor temperature
continued >>
# Code Description
[7.7.2.1] [0-00]
[0-01]
[0-02]
[0-03]
<< continuation
[0-03]: Low outdoor ambient
temperature. –40°C~+5°C (default:
10°C)
[0-02]: High outdoor ambient
temperature. 10°C~25°C (default:
15°C)
[0-01]: Desired leaving water
temperature when the outdoor
temperature equals or drops below
the low ambient temperature.
[9‑05]°C~[9‑06]°C (default: 45°C).
Note: This value should be higher
than [0-00] as for low outdoor
temperatures warmer water is
required.
[0-00]: Desired leaving water
temperature when the outdoor
temperature equals or rises above
the high ambient temperature.
[9‑05]°C~min(45, [9‑06])°C (default:
35°C).
Note: This value should be lower
than [0-01] as for high outdoor
temperatures less warm water is
required.
# Code Description
[7.7.2.2] [0-04]
[0-05]
[0-06]
[0-07]
Set weather-dependent cooling:
[0-04]
[0-05]
T
a
T
t
[0-07] [0-06]
T
t
: Target leaving water temperature
(additional)
T
a
: Outdoor temperature
continued >>