2-2 ELECTRICAL SPECIFICATIONS EKHBH016AB EKHBX016AB
Electric heater Type 3V3
Power Supply Phase 1~
Frequency
Hz 50 50
Voltage V 230 230
Current back-up
heater
Running
Current
A13 13
Current back-up
heater + booster
heater (EKHWS*
models)
Z-max Text 0.29 0.29
Running Current *V3 A 26 (13+13)
Minimum Ssc value *V3 Equipment complying with EN/IEC 61000-3-12 **
Electric heater Voltage range Minimum -10%
Maximum +10%
Wiring connections For power supply
backup heater
Quantity of wires 3G
Type of wires Select diameter and type according to national and local regulations
Electric heater Type 6V3
Power Supply Phase 1~
Frequency
Hz 50 50
Voltage V 230 230
Current back-up
heater
Running
Current
A26 26
Current back-up
heater
Z-max Text 0.29 0.29
Electric heater Current back-up
heater
Minimum Ssc value Equipment complying with EN/IEC 61000-3-12 **
Current back-up
heater + booster
heater (EKHWS*
models)
Z-max Text 0.17 0.17
Running Current *V3 A 39 (26+13)
Minimum Ssc value *V3 Equipment complying with EN/IEC 61000-3-12 **
Electric heater Voltage range Minimum -10%
Maximum +10%
Wiring connections For power supply
backup heater
Quantity of wires 3G
Type of wires Select diameter and type according to national and local regulations
Electric heater Type 6WN
Power Supply Phase 3~
Frequency
Hz 50 50
Voltage V 400 400
Current back-up
heater
Running
Current
A8.7 8.7
Current back-up
heater + booster
heater (EKHWS*
models)
Running Current *V3 A 21,7 (8.7+13)
*Z2 A 16.2 (8.7+7.5)
Minimum Ssc value *V3 Equipment complying with EN/IEC 61000-3-12 **
*Z2 Equipment complying with EN/IEC 61000-3-12 **
Electric heater Voltage range Minimum -10%
Maximum +10%
Wiring connections For power supply
backup heater
Quantity of wires 4G
Type of wires Select diameter and type according to national and local regulations
Electric heater Type 6T1
Power Supply Phase 3~
Frequency
Hz 50 50
Voltage V 230 230
Current back-up
heater
Running
Current
A 15.1 15.1
Current back-up
heater + booster
heater (EKHWS*
models)
Running Current *V3 A 26.1 (15.1+13)
Minimum Ssc value *V3 Equipment complying with EN/IEC 61000-3-12 **
Electric heater Voltage range Minimum -10%
Maximum +10%
Wiring connections For power supply
backup heater
Quantity of wires 4G
Type of wires Select diameter and type according to national and local regulations