Specifications ESIE09-08A
10 Specifications
Electrical Specifications
Power Supply Name EKHBRD(011/014/016)AA/AB/
ACV1
EKHBRD(011/014/016)AA/AB/
ACY1
11 14 16 11 14 16
Phase 1~ 3~
Frequency Hz 50 50
Voltage V 220-240 380-415
Voltage Range Minimum V 198 342
Maximum V 254 440
Current Z-max
(2)
Ω 0,34 0,32 0,32 -
Minimum Ssc
(3)
value kVa Equipment complying with EN/IEC
61000-3-12
(1)
-
Maximum
running Current
Heating A
22,5 23,8 23,8 12,5
Recommended fuses A 25 16
Wiring
Connections
For power
supply
Quantity 2G 4G
Wire type Note
(4)
Note
(4)
For power
supply
(5)
Quantity 2G + 2G 4G + 2G
Wire type Note
(4)
Note
(4)
For connection
with outdoor
unit
Quantity 2
Remark
F1+F2
Power Supply Intake Both indoor unit and outdoor unit
Notes
(1): European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems
with input current > 16A and
75A per phase
(2): In accordance with EN/IEC 61000-3-11
(6)
, it may be necessary to consult the distribution network operator to ensure that the equipment is
connected only to a supply with Zsys
(7)
Zmax
(3): Short-circuit power
(4): Select diameter and type according to national and local regulations
(5): In case of benefit kWh rate power supply installations
(6): European/International Technical Standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply
systems for equipment with rated current 75A
(7): System impedance