Field Setting ESIE09-08A
92 Test Operation
EKHBRD*AB/AC
First
code
Second
code Setting name
Installer setting at variance with
default value
Default
value Range Step UnitDate Value Date Value
0 Remote control setup
00 User permission level 2 2~3 1
01 Room temperature compensation value 0 –5~5 0.5 °C
02 Not applicable. Do not change the default value. 1 (ON) 0/1
03 Status: space heating schedule timer mode 1 (ON) 0/1
1 Automatic storage timing for domestic water heating
00 Status: night time storage 1 (ON) 0/1
01 Night time storage start time 1:00 0:00~
23:00
1:00 hour
02 Status: day time storage 0 (OFF) 0/1
03 Day time storage start time 15:00 0:00~
23:00
1:00 hour
2 Automatic setback function
00 Status: setback operation 1 (ON) 0/1
01 Setback operation start time 23:00 0:00~
23:00
1:00 hour
02 Setback operation stop time 5:00 0:00~
23:00
1:00 hour
3 Weather dependent set point
00 Low ambient temperature (Lo_A) –10 –20~5 1 °C
01 High ambient temperature (Hi_A) 15 10~20 1 °C
02 Set point at low ambient temperature (Lo_Ti) 70 25~80 1 °C
03 Set point at high ambient temperature (Hi_Ti) 45 25~80 1 °C
4 Disinfection function
00 Status: disinfection operation 1 (ON) 0/1
01 Disinfection operation day selection Fri Mon~Sun
02 Disinfection operation start time 23:00 0:00~
23:00
1:00 hour
5 Automatic setback and disinfection set point
00 Set point: disinfection operation temperature 70 60~70 5 °C
01 Disinfection operation time duration 10 5~60 5 min
02 Leaving water setback temperature 5 0~10 1 °C
03 Room setback temperature 18 17~23 1 °C
6 Option setup
00 Domestic hot water tank installed 0 (OFF) 0/1
01 Optional room thermostat installed 0 (OFF) 0/1
02 Backup heater kit activation 0 (OFF) 0/1
03 Solar kit activation 0 (OFF) 0/1
04 Benefit kWh power supply mode 0 0/2 1
7 Option setup
00 Optional bottom plate heater installed 1 (ON) 0/1
01 Not applicable. Do not change the default value. 0 (OFF) 0/1
02 Multiple set point pattern 0 (A) 0/1
03 Multiple set point 1 0 (OFF) 0/1
04 Multiple set point 2 0 (OFF) 0/1