ESIE09-08A Field Setting
Test Operation 93
8 Option setup
00 Remote controller temperature control 1 (ON) 0/1
01 Backup heater kit optional setting 1 (ON) 0/1
02 Emergency mode 0 (OFF) 0/1
03 Status: low noise level 1 1~3 1
04 Status: freeze up prevention 0 0~2 1
9 Automatic temperature compensation
00 Leaving water temperature compensation value 0 –5~5 0.5 °C
01 Domestic hot water tank compensation value 0 –5~5 0.5 °C
02 Thermo ON/OFF admission 0 –5~5 0.5 °C
A Option setup
00 Current limitation 0 0~2 1
01 Not applicable. Do not change the default value. 0 0~2 1
02 Set point: required temperature difference for
leaving and returning water
10 5~15 1 °C
03 Set point: multiple set point 1 required
temperature value
35 25~80 1 °C
04 Set point: multiple set point 2 required
temperature value
65 25~80 1 °C
B Domestic hot water set points
00 Set point: reheat minimum temperature 35 35~65 1 °C
01 Set point: reheat maximum temperature 45 35~75 1 °C
02 Status: weather dependent domestic water
heating
1 (ON) 0/1
03 Set point: storage temperature 70 45~75 1 °C
04 Automatic maximum domestic hot water storage
temperature
70 55~75 1 °C
C Leaving water temperature limits
00 Set point: leaving water maximum temperature 80 37~80 1 °C
01 Set point: leaving water minimum temperature 25 25~37 1 °C
02 Not applicable. Do not change the default value. 20 18~22 1 °C
03 Not applicable. Do not change the default value. 5 5~18 1 °C
D Domestic water heating retention times
00 Set point: minimum time for domestic water
heating
10 5~20 1
01 Set point: maximum time for domestic water
heating
30 10~60 5
02 Set point: interval minimum stop time of
domestic water heating
15 5~30 5
E Service mode
00 Vacuum mode 0 0/1
01 Not applicable. Do not change the default value. 0 (OFF) 0/1
02 Not applicable. Do not change the default value. 0 (OFF) 0/1
03 Not applicable. Do not change the default value. 1 0~2 1
04 Pump only operation 0 0~2 1
First
code
Second
code Setting name
Installer setting at variance with
default value
Default
value Range Step UnitDate Value Date Value