User reference guide
24
BRC0731A4
3P422724-1
Menu Manipulation
4
NoYes
Energy Saving List
Save the settings?
SettingReturn
Press the (Left/Right) buttons to select Yes .
Press the Menu/Enter button to conrm the
settings and to return to the Basic Screen.
Setpoint Range Setting
1
Energy Saving List
Setpoint Range
Setback Condition
Setpoint Auto Reset
Off Timer
Energy Saving Options
SettingReturn
Display the Energy Saving Options (See "Energy
Saving List" on page 23).
Press the
(Up/Down) buttons to select
Setpoint Range and press the Menu/Enter
button.
2
18°C – 32°C
10°C – 30°C
18°C – 30°C
Setpoint Range
SettingReturn
Cool
Heat
Auto
Press the (Up/Down) buttons to change the
cooling or heating temperature setpoint range.
Move the cursor using the
(Left/Right)
buttons.
Press the Menu/Enter button when all changes are
made. The conrmation screen will appear.
Note
The default setpoint range restriction is [18°C→32°C] for cooling, [10°C→30°C] for heating,
and [18°C→30°C] for auto. This setpoint range is the general setpoint range and is as a result
always active regardless of whether Setpoint Range is enabled or disabled.
The default setpoint range for setback operation is [33°C→37°C] for cooling and [10°C→15°C]
for heating. This setpoint range cannot be changed.
3
NoYes
Setpoint Range
Save the settings?
SettingReturn
Press the (Left/Right) buttons to select Yes .
Press the Menu/Enter button to conrm the
settings and to return to the Basic Screen.
Operation Method
This function should not be used when a centralised controller is connected
via the KRP928 Interface adapter for Room Air Conditioner.