22
APPENDIX A BLOWER PERFORMANCE DATA
12.5 TON AC
DBC150*V STANDARD STATIC HORIZONTAL
                 
0.1
5229 865 2.69 4949 822 2.46 4665 777 1.76 4384 732 1.57 4080 686 1.21
0.2
5101 865 2.60 4809 822 2.36 4515 777 1.67 4218 732 1.48 3896 686 1.14
0.3
5254 905 3.03 4959 865 2.50 4652 822 2.25 4345 777 1.58 4028 732 1.38
0.4
5105 905 2.91 4803 865 2.40 4478 822 2.14 4154 777 1.48 3812 732 1.28
0.5
4949 905 2.78 4634 865 2.28 4288 822 2.02 3943 777 1.37
0.6
4784 905 2.65 4451 865 2.16 4080 822 1.89
0.7
4610 905 2.52 4254 865 2.04 3856 822 1.76
0.8
4429 905 2.39 4043 865 1.91

O

3
DBC150*S HIGH STATIC HORIZONTAL
1
     
           
0.8
6164 1068 5.04 5873 1030 4.06 5526 990 3.36 5160 948 3.00
0.9
6051 1068 4.91 5736 1030 3.92 5379 990 3.23 4977 948 2.85
1.0
5925
1068 4.76 5582 1030 3.77 5205 990 3.09 4770 948 2.69
1.1
5783 1068 4.61 5412 1030 3.61 5004 990 2.92 4539 948 2.51
1.2
6017 1106 4.93 5628 1068 4.43 5225 1030 3.43 4778 990
2.75 4285 948 2.33
1.3
5858 1106 4.75 5457 1068 4.25 5023 1030 3.24 4525 990 2.55 4007 948 2.13
1.4
6019 1144 4.99 5691 1106
4.56
5273
1068 4.06 4803 1030 3.05
4246
990 2.35
1.5
5864 1144 4.81 5514 1106 4.37 5074 1068 3.85 4568 1030 2.85
3940 990 2.14
1.6
5700 1144 4.63 5328 1106 4.17 4860 1068 3.64 4316 1030 2.64
1.7
5528 1144 4.45 5133 1106 3.97 4632 1068 3.42 4047 1030 2.43
1.8
5348 1144 4.26 4928 1106 3.77 4389 1068 3.19 3762 1030 2.22

O

3
1
To operate below 0.8" H
2
O external static pressure, motor and blower sheave must be changed to VP44 and AK79H respectively, or equivalents
DBC150*V STANDARD STATIC DOW NSHOT
     
           
0.1
5638 777 2.36 5275 732 2.09 4903 686 1.59
0.2
5432 777 2.22 5059 732 1.95 4676 686 1.48
0.3
5615 822 2.94 5212 777 2.08 4821 732 1.81 4413 686 1.36
0.4
5760 865 3.09 5392 822 2.77 4979 777 1.94 4562 732 1.67 4112 686 1.23
0.5
5555 865 2.94 5164 822 2.61 4733 777 1.80 4282 732 1.51 3775 686 1.09
0.6
5342 865 2.78 4931 822 2.44 4472 777 1.65 3981 732 1.36
0.7
5123 865 2.62 4691 822 2.28 4199 777 1.50
0.8
4897 865 2.46 4446 822 2.12 3912 777 1.36

O

3
DBC150*S HIGH STATIC DOWNSHOT
1

    
           
0.8
6028 990 3.81 5535 948 3.31
0.9
5810 990 3.61 5306 948 3.12
1.0
6254 1030
4.46 5577 990 3.40 5055 948
2.91
1.1
6054 1030 4.25
5328 990
3.19
4783 948 2.70
1.2
5844 1030 4.03 5063 990 2.97 4489 948 2.48
1.3
6028 1068 4.88 5624 1030 3.81 4783 990 2.75 4174 948 2.25
1.4
5803 1068 4.63 5394 1030 3.59 4487 990 2.53 3837 948 2.02
1.5
6145 1106
5.07 5568 1068 4.37 5155 1030 3.37 4175 990 2.30
1.6
5939 1106 4.84 5323 1068 4.11 4905 1030 3.14 3848 990 2.08
1.7
5725 1106 4.60 5068 1068 3.85 4646 1030 2.91
1.8
5969 1144 4.93 5505 1106 4.36 4803 1068 3.58 4377 1030 2.69
1
To operate below 0.8" H
2
O external static pressure, motor and blower sheave must be changed to VP44 and AK79H respectively, or equivalents

O

3