11 | Configuration
Installer reference guide
168
ERLA11~16D + EBBH/X11+16D
Daikin Altherma 3 R W
4P643603-1B – 2022.05
Types of weather-dependent curve
There are 2 types of weather-dependent curves:
2-points curve
Slope-offset curve
Which type of curve you use to make adjustments, depends on your personal
preference. See "11.5.4Using weather-dependent curves"[4170].
Availability
The weather-dependent curve is available for:
Main zone - Heating
Main zone - Cooling
Additional zone - Heating
Additional zone - Cooling
Tank (only available to installers)
INFORMATION
To operate weather-dependent, correctly configure the setpoint of the main zone,
additional zone or tank. See "11.5.4Using weather-dependent curves"[4170].
11.5.2 2-points curve
Define the weather-dependent curve with these two setpoints:
Setpoint (X1, Y2)
Setpoint (X2, Y1)
Example
Y1
Y2
X1 X2
a