EasyManua.ls Logo

Daikin EBBX-D9W - Page 191

Daikin EBBX-D9W
316 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11 | Configuration
Installer reference guide
191
ERLA11~16D + EBBH/X11+16D
Daikin Altherma 3 R W
4P643603-1B – 2022.05
Emitter type
Additional zone
Space heating setpoint
range [9‑05]~[9‑06]
Target delta T in heating
[1‑0C]
0: Underfloor
heating
Maximum 55°C Variable (see [3.B.1])
1: Fancoil unit Maximum 55°C Variable (see [3.B.1])
2: Radiator Maximum 60°C Fixed 8°C
Setpoint range
For more information about Setpoint range, see "11.6.3Main zone"[4177].
# Code Description
Leaving water temperature range for the additional leaving water temperature
zone (= the leaving water temperature zone with the highest leaving water
temperature in heating operation and the lowest leaving water temperature in
cooling operation)
[3.8.1] [9-05] Heating minimum: 15°C~37°C
[3.8.2] [9-06] Heating maximum
[2‑0D]=2 (emitter type additional zone =
radiator)
37°C~60°C
Else: 37°C~55°C
[3.8.3] [9-07] Cooling minimum
5°C~18°C
[3.8.4] [9-08] Cooling maximum
18°C~22°C
Control
The control type for the additional zone is read only. It is determined by the control
type of the main zone.
See "11.6.3Main zone"[4177].
# Code Description
[3.9] N/A Control:
Leaving water if the control type of the
main zone is Leaving water.
External room thermostat if the control
type of the main zone is:
- External room thermostat,or
- Room thermostat.
Ext thermostat type
Only applicable in external room thermostat control.
Also see "11.6.3Main zone"[4177].

Table of Contents

Related product manuals