11 | Configuration
Installer reference guide
226
ERLA11~16D + EBBH/X11+16D
Daikin Altherma 3 R W
4P643603-1B – 2022.05
Timers
For simultaneous space and domestic hot water operation request.
[8-02]: Anti-recycle timer
t
1
0
1
0
[8-01] [8-02]
1 Heat pump domestic water heating mode (1=active, 0=not active)
2 Hot water request for heat pump (1=request, 0=no request)
t Time
[8-04]: Additional timer at [4-02]/[F-01]
t
T
A
t
T
A
0
[8-01]
[5-03] [4-02]
[8-02]
[8-01]+
[8-04]
0
[8-01]
[F-01] 35°C
[8-02]
[8-01]+
[8-04]
T
A
Ambient (outdoor) temperature
t Time
Anti-recycle timer
Maximum running time domestic hot water
# Code Description
[9.6.4] [8-02] Anti-recycle timer: Minimum time
between two cycles for domestic hot water. The
actual anti-recycling time also depends on setting
[8-04].
Range: 0~10 hours
Remark: The minimum time is 0.5 hours even
when the selected value is 0.
[9.6.5] [8-00] Minimum running timer:
Do NOT change.