11 | Configuration
Installer reference guide
171
EWAA011~016DA + EWYA009~016DA
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P620242-1 – 2020.06
# Code Description
[9.9.1] [4-08] Power consumption control:
0 No: Disabled.
1 Continuous: Enabled: You can set one
power limitation value (in A or kW) to which
the system power consumption will be
limited for all the time.
2 Inputs: Enabled: You can set up to four
different power limitation values (in A or kW)
to which the system power consumption will
be limited when the corresponding digital
input asks.
[9.9.2] [4-09] Type:
0 Amp: The limitation values are set in A.
1 kW: The limitation values are set in kW.
Limit when [9.9.1]=Continuous and [9.9.2]=Amp:
# Code Description
[9.9.3] [5-05] Limit: Only applicable in case of full time
current limitation mode.
0A~50A
Limits when [9.9.1]=Inputs and [9.9.2]=Amp:
# Code Description
[9.9.4] [5-05] Limit 1: 0A~50A
[9.9.5] [5-06] Limit 2: 0A~50A
[9.9.6] [5-07] Limit 3: 0A~50A
[9.9.7] [5-08] Limit 4: 0A~50A
Limit when [9.9.1]=Continuous and [9.9.2]=kW:
# Code Description
[9.9.8] [5-09] Limit: Only applicable in case of full time
power limitation mode.
0kW~20kW
Limits when [9.9.1]=Inputs and [9.9.2]=kW:
# Code Description
[9.9.9] [5-09] Limit 1: 0kW~20kW
[9.9.A] [5-0A] Limit 2: 0kW~20kW
[9.9.B] [5-0B] Limit 3: 0kW~20kW
[9.9.C] [5-0C] Limit 4: 0kW~20kW
Priority heater
This setting defines the priority of the electrical heaters depending on applicable
limitation. As no booster heater is present, the backup heater will always be
prioritised.