6 | Application guidelines
Installer reference guide
44
EWAA011~016DA + EWYA009~016DA
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P620242-1 – 2020.06
6.4 Setting up the energy metering
▪ Via the user interface, you can read out the following energy data:
- Produced heat
- Consumed energy
▪ You can read out the energy data:
- For space cooling
- For space heating
▪ You can read out the energy data:
- Per month
- Per year
INFORMATION
The calculated produced heat and consumed energy are an estimation, the accuracy
cannot be guaranteed.
6.4.1 Produced heat
INFORMATION
The sensors used to calculate the produced heat are calibrated automatically.
INFORMATION
If glycol is present in the system ([E‑0D]=1]), then the produced heat will NOT be
calculated, nor will it be displayed on the user interface.
▪ The produced heat is calculated internally based on:
- The leaving and entering water temperature
- The flow rate
▪ Setup and configuration: No additional equipment needed.
6.4.2 Consumed energy
You can use the following methods to determine the consumed energy:
▪ Calculating
▪ Measuring
INFORMATION
You cannot combine calculating the consumed energy (example: for backup heater
(if applicable)) and measuring the consumed energy (example: for outdoor unit). If
you do so, the energy data will be invalid.
Calculating the consumed energy
▪ The consumed energy is calculated internally based on:
- The actual power input of the outdoor unit
- The set capacity of the optional backup heater
- The voltage