11 | Configuration
Installer reference guide
173
EWAA011~016DA + EWYA009~016DA
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P620242-1 – 2020.06
# Code Description
[9.A.1] [D‑08] Electricity meter 1:
0 None: NOT installed
1 1/10kWh: Installed
2 1/kWh: Installed
3 10/kWh: Installed
4 100/kWh: Installed
5 1000/kWh: Installed
[9.A.2] [D‑09] Electricity meter 2:
0 None: NOT installed
1 1/10kWh: Installed
2 1/kWh: Installed
3 10/kWh: Installed
4 100/kWh: Installed
5 1000/kWh: Installed
In case of pulse meter for photovoltaic panels:
6 100/kWh for PV panel: Installed
7 1000/kWh for PV panel: Installed
Sensors
External sensor
# Code Description
[9.B.1] [C–08] External sensor: When an optional external
ambient sensor is connected, the type of the
sensor must be set.
0 None : NOT installed. The thermistor in the
user interface and in the outdoor unit are used
for measurement.
1 Outdoor: Connected to the hydro PCB of the
outdoor unit measuring the outdoor
temperature. Remark: For some functionality,
the temperature sensor in the outdoor unit is
still used.
2 Room: Connected to the hydro PCB of the
outdoor unit measuring the indoor
temperature. The temperature sensor in the
user interface is NOT used anymore. Remark:
This value has only meaning in room
thermostat control.
Ext. amb. sensor offset
ONLY applicable in case an external outdoor ambient sensor is connected and
configured.