11 | Configuration
Installer reference guide
179
EWAA011~016DA + EWYA009~016DA
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P620242-1 – 2020.06
# Code Description
[9.F] [E‑08] Power saving function for compressor
module:
0: No
1: Yes
Forced defrost
Forced defrost
Manually start a defrost operation.
# Code Description
[9.H] N/A Do you want to start a defrost operation?
Back
OK
NOTICE
Forced defrost start-up. You can only start forced defrost when the heating
operation has been running for a while.
Overview field settings
All settings can be done using the menu structure. If for any reason it is required to
change a setting using the overview settings, then the overview settings can be
accessed in the field settings overview [9.I]. See "To modify an overview
setting"[4107].
Export MMI settings
About exporting the configuration settings
Export the configuration settings of the unit to a USB memory stick, via the MMI
(the user interface delivered as accessory). When troubleshooting, these settings
can be provided to our Service department.
# Code Description
[9.N] N/A Your MMI settings will be exported
to the connected storage device:
Back
OK
To export MMI settings
1 Insert a USB memory stick in the user interface.
2 On the user interface, go to [9.N] Export MMI settings.