6 | Application guidelines
Installer reference guide
30
EWAA011~016DA + EWYA009~016DA
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P620242-1 – 2020.06
Underfloor heating or radiators – Wireless room thermostat
Setup
b
a
A
B
c
A Main leaving water temperature zone
B One single room
a User interface (delivered as accessory)
b Receiver for wireless external room thermostat
c Wireless external room thermostat
For more information about connecting the electrical wiring to the unit, see
"9.2Connections to the outdoor unit"[478].
The underfloor heating or radiators are directly connected to the outdoor unit
or to the external backup heater kit, if there is one.
The room temperature is controlled by the wireless external room thermostat
(optional equipment EKRTR1).
Configuration
Setting Value
Unit temperature control:
#: [2.9]
Code: [C-07]
1 (External room thermostat):
Unit operation is decided by the
external thermostat.
Number of water temperature zones:
#: [4.4]
Code: [7-02]
0 (Single zone): Main
External room thermostat for the main
zone:
#: [2.A]
Code: [C-05]
1 (1 contact): When the used
external room thermostat can only send
a thermo ON/OFF condition. No
separation between heating or cooling
demand.
Benefits
Wireless. The Daikin external room thermostat is available in a wireless version.
Efficiency. Although the external room thermostat only sends ON/OFF signals, it
is specifically designed for the heatpump system.
Comfort. In case of underfloor heating, the wireless external room thermostat
prevents condensation on the floor during cooling operation by measuring the
room humidity.