6 | Application guidelines
Installer reference guide
32
EWAA011~016DA + EWYA009~016DA
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P620242-1 – 2020.06
Stylish.
Combination: Underfloor heating + Fan coil units
Space heating is provided by:
- The underfloor heating
- The fan coil units
Space cooling is provided by the fan coil units only. The underfloor heating is shut
off by the shut-off valve.
Setup
A
M1
B
a
b
A Main leaving water temperature zone
B One single room
a User interface (delivered as accessory)
b Remote controller of the fan coil units
For more information about connecting the electrical wiring to the unit, see
"9.2Connections to the outdoor unit"[478].
The fan coil units are directly connected to the outdoor unit or to the external
backup heater kit, if there is one.
A shut-off valve (field supply) is installed before the underfloor heating to
prevent condensation on the floor during cooling operation.
The desired room temperature is set via the remote controller of the fan coil
units.
The space heating/cooling demand signal is sent to one digital input on the
outdoor unit (X2M/35 and X2M/30).
The space operation mode is sent by one digital output (X2M/4 and X2M/3) on
the outdoor unit to:
- The fan coil units
- The shut-off valve
Configuration
Setting Value
Unit temperature control:
#: [2.9]
Code: [C-07]
1 (External room thermostat):
Unit operation is decided by the
external thermostat.
Number of water temperature zones:
#: [4.4]
Code: [7-02]
0 (Single zone): Main