6 | Application guidelines
Installer reference guide
34
EWAA011~016DA + EWYA009~016DA
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P620242-1 – 2020.06
The room temperature of the main room is controlled by the dedicated Human
Comfort Interface (BRC1HHDA used as room thermostat).
A thermostatic valve is installed before the underfloor heating in each of the
other rooms.
INFORMATION
Mind situations where the main room can be heated by another heating source.
Example: Fireplaces.
Configuration
Setting Value
Unit temperature control:
#: [2.9]
Code: [C-07]
2 (Room thermostat): Unit operation
is decided based on the ambient
temperature of the dedicated Human
Comfort Interface.
Number of water temperature zones:
#: [4.4]
Code: [7-02]
0 (Single zone): Main
Benefits
Easy. Same installation as for one room, but with thermostatic valves.
Underfloor heating – Multiple external room thermostats
Setup
M1
M2
CB
b
c
b
a
A
A Main leaving water temperature zone
B Room 1
C Room 2
a User interface (delivered as accessory)
b External room thermostat
c Bypass valve
For more information about connecting the electrical wiring to the unit, see
"9.2Connections to the outdoor unit"[478].
For each room, a shut-off valve (field supplied) is installed to avoid leaving water
supply when there is no heating or cooling demand.
A bypass valve must be installed to make water recirculation possible when all
shut-off valves are closed. To guarantee reliable operation, provide a minimum
water flow as described in table "To check the water volume and flow rate" in
"8.1Preparing water piping"[462].