6 | Application guidelines
Installer reference guide
36
EWAA011~016DA + EWYA009~016DA
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P620242-1 – 2020.06
The user interface connected to the outdoor unit decides the space operation
mode. Mind that the operation mode on each room thermostat must be set to
match the outdoor unit.
The room thermostats are connected to the shut-off valves. They are also
connected to the outdoor unit (X2M/35 and X2M/30) -via a relay (field supplied)-
to give feedback when operation is needed. The outdoor unit will supply leaving
water as soon as there is a request from one of the rooms.
Configuration
Setting Value
Unit temperature control:
#: [2.9]
Code: [C-07]
1 (External room thermostat):
Unit operation is decided by the
external thermostat.
Number of water temperature zones:
#: [4.4]
Code: [7-02]
0 (Single zone): Main
External room thermostat for the main
zone:
#: [2.A]
Code: [C-05]
1 (1 contact): When the used
external room thermostat can only send
a thermo ON/OFF condition. No
separation between heating or cooling
demand.
Benefits
Compared with radiators for one room:
Comfort. You can set the desired room temperature, including schedules, for
each room via the room thermostats.
Fan coil units – Multiple rooms
Setup
a
B C
A
bb
A Main leaving water temperature zone
B Room 1
C Room 2
a User interface (delivered as accessory)
b Remote controller of the fan coil units
For more information about connecting the electrical wiring to the unit, see
"9.2Connections to the outdoor unit"[478].
The desired room temperature is set via the remote controller of the fan coil
units.
The user interface connected to the outdoor unit decides the space operation