Error Codes: System Malfunctions ESIE05-04
3–46 Part 3 Troubleshooting
3
1
3
4
5
3.2 Malfunction of Transmission between Indoor and Outdoor Unit (
U4
or
UF
)
Error code U4 or UF
Error generation The error is generated when the microprocessor detects that the transmission between the indoor and
the outdoor unit is not normal over a certain amount of time.
Causes The possible causes are:
Q Wiring indoor-outdoor transmission wire is incorrect
Q Malfunctioning indoor unit PCB
Q Malfunctioning outdoor unit PCB
Q Outside cause (noise...).
Troubleshooting 1 Diagnosis of incorrect or broken/disconnected wiring. If the LEDs on the indoor unit PC board are off,
it indicates that the transmission wiring between indoor and outdoor units may be incorrect or
broken/disconnected.
Caution Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Turnthepowersupplyoff
onceandthenbackon.
Checkof
indoorunit
microcomputer
normal
HAP
Checkof
indoorunit
transmission
malfunction
HBP
FailureofindoorunitPCBor
malfunctionofpowersupply
system.
Resetsnormally.
Couldbeoutsidecause(noise...).
FailureofindoorunitPCB.
Wirecorrectly.
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO(OFF)
NO(ONorOFF)
Tooutdoorunit
(nextpage)
IsHAPflashing?
IsHAPflashing?
Is
indoor-outdoor
transmissionwire
connected
correctly?
Does
outdoorunit
microcomputer
normalH1P
flash?
IsH2Pon?
IsH1Pflashing?