Loading...
Disassembly and Maintenance ESIE05-04
5–40 Part 5 – Disassembly and Maintenance
3
1
5
5
[Installation procedure of
drain pump or float switch]
1 Install a spare drain
pump or float switch on
the mounting plate, then
firmly secure the lead
wires using the provided
clamp materials (3
pieces).
2 Connect the lead wires of
the drain pump or float
switch in the original
state, firmly secure the
aforementioned clamp
materials (screw type
fixing) to the drain pan
with the use of mounting
screws.
Step
Procedure Points
Mounting screw
(For float switch)
Float
switch
Float switch
lead wire
Mounting plate
Provided clamp material
(for bundling)
(Fix to the hole in the
mounting plate)
Drain pump
lead wire
Provided clamp
material
(for bundling)
Provided mounting screw
(for drain pump)
Pay attention to the mounting
direction of clamp material.
1mm or less
Provided clamp material
(for fixing screw)
(Fix the lead wires each
other.)
Mounting
screw
Drain
Pan
Clamp material
(for fixing screw)
Engage with the fixing tabs (5 tabs)
Drain pump

Table of Contents