ESIE05-04 Disassembly and Maintenance
Part 5 – Disassembly and Maintenance 5–93
3
5
1
5
1.13.7 Removal of Swing Motor
Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step Procedure Points
1 Remove the screw from
the right side panel. Slide
the right side panel
toward the front and
detach it.
2 Cut off the tie-wrap of the
swing motor connector.
3 Disconnect the
connector from the swing
motor connector.
4 Remove the screw from
the swing motor. The
swing motor has two
projections on it. Lower
the swing motor and take
it out.
Q When reassembling, fit the
horizontal blade shaft end to
the D-profiled bearing.
Apply the tie-wrap to the
connectors to secure them in
place.