1-13
English
L
N
COMP
N
L
R
S
N
L
COMP
Indoor Unit
Terminal Block
Interconnection Cable
Outdoor Unit
Terminal Block
Power Supply Cable
Model Indoor (FCRN) 50E 60E 71E
Outdoor (RN/RR) 50C 60C 71C
Voltage range** Indoor (FCRN)
220-240V/1Ph/50Hz + !
Outdoor (RN/RR)
220-240V/1Ph/50Hz + !
Power supply cable size* (mm
2
)
Number of conductors
2.5
3
2.5
3
4.0
3
Interconnection cable size* (mm
2
)
Number of conductors
2.5
3
2.5
3
2.5
3
Recommended time delay fuse* (A) 13 18 25
COMP
N1
L
N
COMP
N
Interconnection Cable
Indoor Unit
Terminal Block
Outdoor Unit
Terminal Block
Power Supply Cable
ELECTRICAL WIRING CONNECTION
IMPORTANT :
* These values are for information only. They should be checked and selected to comply with local and/or
national codes and regulations. They are also subject to the type of installation and size of conductors.
** The appropriate voltage range should be checked with data label on the unit.
FCRN 50/60E - RN 50/60C (1 PH)
FCRN 71E - RR 71C (1 PH)
There must be an all pole disconnection
in the supply mains with a contact
separation of at least 3mm.
There must be an all pole disconnection
in the supply mains with a contact
separation of at least 3mm.
FCRN 100E - RR 90/100D (1 PH)
1 IM-5CKE-0912(0)DAIKIN-EN.indd 131 IM-5CKE-0912(0)DAIKIN-EN.indd 13 9/28/12 2:04:18 PM9/28/12 2:04:18 PM