12
Sound Data
Sound Data
Sound Pressure Level
Model Speed
1/1 Octave Sound Pressure (dB, ref 20μPa)
Overall
(dBA)
Noise
Criteria
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
FCRN18FXV1S
High 43 39 38 31 25 18 8 38 33
Medium 42 37 34 28 22 14 7 35 29
Low 42 35 31 26 20 14 7 33 25
Quiet 41 28 25 22 17 12 5 29 21
FCRN24FXV1S
High 43 41 40 35 32 25 14 41 35
Medium 41 40 37 31 28 19 11 38 32
Low 40 37 34 28 24 16 11 35 29
Quiet 38 34 30 26 21 15 11 32 24
FCRN30FXV1S
High 47 46 45 41 35 30 21 46 40
Medium 47 41 40 35 30 25 18 41 35
Low 46 37 35 31 24 22 17 37 30
Quiet 44 34 32 26 22 21 17 34 26
FCRN36FXV1S
High 51 48 46 43 38 34 22 48 42
Medium 51 45 43 40 34 29 18 45 39
Low 51 41 39 34 29 24 15 41 34
Quiet 49 37 34 29 23 18 11 37 31
FCRN42FXV1S
High 51 48 46 43 38 34 22 48 42
Medium 51 45 43 40 34 29 18 45 39
Low 51 41 39 34 29 24 15 41 34
Quiet 49 37 34 29 23 18 11 37 31
FCRN45FXV1S
High 51 48 46 43 38 34 22 48 42
Medium 51 45 43 40 34 29 18 45 39
Low 51 41 39 34 29 24 15 41 34
Quiet 49 37 34 29 23 18 11 37 31
Model Measuring Location
FCRN18FXV1S
FCRN24FXV1S
Microphone
1.4m
Standard : JIS C 9612
FCRN30FXV1S
FCRN36FXV1S
FCRN42FXV1S
FCRN45FXV1S
Microphone
1.5m
Standard: JIS B 8616