2 | General safety precautions
Installer and user reference guide
10
FDA125A5VEB
Split system air conditioners
4P495031-1B – 2022.10
NOTICE
Protect pipework from physical damage.
Keep the pipework installation to a minimum.
To determine the minimum floor area
1 Determine the total refrigerant charge in the system (= factory refrigerant
charge + additional refrigerant amount charged).
Contains fluorinated greenhouse gases
2
1
1
1
2
2
kg
tCO
2
eq
1000
GWP × kg
=
=
+
kg
=
kg
=
GWP: xxx
R32
2 Determine which graph or table to use.
For indoor units: Is the unit ceiling-mounted, wall-mounted or floor-
standing?
For outdoor units installed or stored indoors, this depends on the installation
height:
If the installation height is… Then use the graph or table for…
<1.8m Floor-standing units
1.8≤x<2.2m Wall-mounted units
≥2.2m Ceiling-mounted units
3 Use the graph or table to determine the minimum floor area.