SiBE121123_A Troubleshooting for RA Indoor Unit
Service Diagnosis 166
Troubleshooting
Check No.01
Refer to P.206
Check No.06
Refer to P.208
YES
YES
NO
NO
NO
NO
NO
(R18421)
YES
Caution
Replace the indoor electronic
expansion valve coil.
Replace the thermistor.
Radiant panel thermistors
Indoor heat exchanger
thermistor
Room temperature
thermistor
Provide sufficient air passage.
YES
Check No. 01
Radiant panel thermistors
Indoor heat exchanger
thermistor
Room temperature thermistor
Check the air passage.
Check the operation condition.
Check the air filter.
OK?
As
described in the
thermistor characteristic
chart?
Is there any short
circuit?
YES
Clean the indoor heat
exchanger.
Very dirty?
YES
Clean the air filter.
Very dirty?
NO
Completed.
Error repeats?
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Check No. 06
Check the indoor electronic
expansion valve coil.
YES
NO
Start operation within the
specified range of the outdoor
temperature.
Condition OK?
Check the indoor heat exchanger.
Replace the indoor unit PCB.
Change the refrigerant to remove
moisture from the piping (after
drawing a vacuum).
YES
NO
Completed.
Replace the indoor heat
exchanger.
Error repeats?
When the outdoor temperature is below the
lower limit for cooling operation (10˚C), the
freeze-up protection control is activated and the
cooling operation stops.

Table of Contents

Other manuals for Daikin FTK15JEVM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FTK15JEVM and is the answer not in the manual?

Daikin FTK15JEVM Specifications

General IconGeneral
BrandDaikin
ModelFTK15JEVM
CategoryHeat Pump
LanguageEnglish

Related product manuals