SiBE121123_A Function of RA Indoor Unit
Function and Control 62
1.7 Program Dry Operation
Outline Program dry operation removes humidity while preventing the room temperature from lowering.
Since the microcomputer controls both the temperature and airflow rate, the temperature
adjustment and [FAN] adjustment buttons are inoperable.
Detail The microcomputer automatically sets the temperature and airflow rate. The difference between
the room thermistor temperature at start-up and the target temperature is divided into two
zones. Then, the unit operates with an appropriate capacity for each zone to maintain the
temperature and humidity at a comfortable level.
Room thermistor
temperature at start-up
Target temperature
X
Thermostat OFF point
Y
Thermostat ON point
Z
24°C or more
Room thermistor
temperature at start-up
X
2.5°C
X
0.5°C
or
Y + 0.5°C (zone B)
continues for 10 min.
23.5°C
X
2.0°C
X
0.5°C
or
Y + 0.5°C (zone B)
continues for 10 min.
~
18°C
18°C X
2.0°C
X
0.5°C = 17.5°C
or
Y + 0.5°C (zone B)
continues for 10 min.
17.5°C
~
Z
X
Y
Zone B
Zone B
Zone A = Thermostat OFF
Zone C = Thermostat ON
+0.5ºC
(R11581)

Table of Contents

Other manuals for Daikin FTK15JEVM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FTK15JEVM and is the answer not in the manual?

Daikin FTK15JEVM Specifications

General IconGeneral
BrandDaikin
ModelFTK15JEVM
CategoryHeat Pump
LanguageEnglish

Related product manuals