Troubleshooting for Outdoor Unit SiBE121123_A
197 Service Diagnosis
Troubleshooting
Check No.15
Refer to P.212
Check No.18
Refer to P.215
Check No.20
Refer to P.216
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
YES
Turn off the power.
Check the connection.
Check the power supply voltage.
Correct the power supply.
Voltage as rated?
(R18319)
NO
NO
NO
YES
YES
NO
YES
YES
Check No. 20
Check the short circuit of the diode
bridge.
Check No.15
Check with the inverter analyzer.
Turn off the power. Disconnect the
harnesses U, V, and W.
Turn on the power.
Check the electrolytic capacitor
voltage.
Electrical
components or
compressor harnesses
connected as
specified?
Replace the outdoor unit
PCB.
Replace the compressor.
Correct the power supply
or replace the outdoor unit
PCB.
Reconnect the electrical
components or compressor
harnesses as specified.
Replace the outdoor unit
PCB.
Inverter analyzer:
RSUK0917C
Normal?
NO
YES
Check No. 18
Check the discharge pressure.
Replace the stop valve.
OK?
320 ± 50 VDC?
Any LED OFF?

Table of Contents

Other manuals for Daikin FTK15JEVM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FTK15JEVM and is the answer not in the manual?

Daikin FTK15JEVM Specifications

General IconGeneral
BrandDaikin
ModelFTK15JEVM
CategoryHeat Pump
LanguageEnglish

Related product manuals