EasyManua.ls Logo

Daikin FTKS50FV1B - Page 41

Daikin FTKS50FV1B
355 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Specifications SiENBE12-713
30 Specifications
Duct Connected Type
50Hz 230V
Note:
1. The operating sound is based on the rear side suction inlet and the external static pressure 40 Pa.
Operating sound for under side suction inlet : [operating sound for rear side suction inlet] +5 dB.
However, when installation to which the external static pressure becomes low is carried out,
5 dB or more may go up.
Model
FDXS25CAVMB FDXS35CAVMB
Cooling Heating Cooling Heating
Rated Capacity 2.5kW Class 3.5kW Class
Front Panel Color
——
Air Flow Rates
m³/min
(cfm)
H 9.5 (335) 9.5 (335) 10.0 (353) 10.0 (353)
M 8.8 (311) 8.8 (311) 9.3 (328) 9.3 (328)
L 8.0 (282) 8.0 (282) 8.5 (300) 8.5 (300)
SL 6.7 (237) 6.7 (237) 7.0 (247) 7.0 (247)
Fan
Type Sirocco Fan Sirocco Fan
Motor Output W 62 62
Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto
Air Filter Removable-Washable-Mildew Proof Removable-Washable-Mildew Proof
Running Current (Rated) A 0.47 0.47 0.47 0.47
Power Consumption (Rated) W 100 100 100 100
Power Factor % 92.5 92.5 92.5 92.5
Temperature Control Microcomputer Control Microcomputer Control
Dimensions (H×W×D) mm 200×900×620 200×900×620
Packaged Dimensions (H×W×D) mm 266×1,106×751 266×1,106×751
Weight kg 25 25
Gross Weight kg 31 31
Operation
Sound
H/M/L/SL dBA 35/33/31/29 35/33/31/29 35/33/31/29 35/33/31/29
External Static Pressure Pa 40 40
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Piping Connection
Liquid mm
φ
6.4
φ
6.4
Gas mm
φ 9.5 φ 9.5
Drain mm VP20 (O.D.
φ 26 / I.D. φ 20) VP20 (O.D. φ 26 / I.D. φ 20)
Drawing No. 3D048945C 3D048946C
Model
FDXS50CVMB FDXS60CVMB
Cooling Heating Cooling Heating
Rated Capacity 5.0kW Class 6.0kW Class
Front Panel Color
——
Air Flow Rates
m³/min
(cfm)
H 12.0 (424) 12.0 (424) 16.0 (565) 16.0 (565)
M 11.0 (388) 11.0 (388) 14.8 (523) 14.8 (523)
L 10.0 (353) 10.0 (353) 13.5 (477) 13.5 (477)
SL 8.4 (297) 8.4 (297) 11.2 (395) 11.2 (395)
Fan
Type Sirocco Fan Sirocco Fan
Motor Output W 130 130
Speed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto
Air Filter Removable-Washable-Mildew Proof Removable-Washable-Mildew Proof
Running Current (Rated) A 0.64 0.64 0.74 0.74
Power Consumption (Rated) W 140 140 160 160
Power Factor % 95.1 95.1 94.0 94.0
Temperature Control Microcomputer Control Microcomputer Control
Dimensions (H×W×D) mm 200×900×620 200×1,100×620
Packaged Dimensions (H×W×D) mm 266×1,106×751 266×1,306×751
Weight kg 27 30
Gross Weight kg 34 37
Operation
Sound
H/M/L/SL dBA 37/35/33/31 37/35/33/31 38/36/34/32 38/36/34/32
External Static Pressure Pa 40 40
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Piping Connection
Liquid mm
φ
6.4
φ
6.4
Gas mm
φ12.7 φ12.7
Drain mm VP20 (O.D.
φ 26 / I.D. φ 20) VP20 (O.D. φ 26 / I.D. φ 20)
Drawing No. 3D052132 3D052133
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3

Table of Contents

Other manuals for Daikin FTKS50FV1B

Related product manuals