1.7 Thermostat Control
Thermostat control is based on the difference between the room temperature and the setpoint.
Thermostat OFF Condition
$ The temperature difference is in the zone A.
Thermostat ON Condition
$ The temperature difference is above the zone C after being in the zone A.
$ The system resumes from defrost control in any zones except A.
$ The operation turns on in any zones except A.
$ The monitoring time has passed while the temperature difference is in the zone B.
(Cooling / Dry : 10 minutes, Heating : 10 seconds)
Cooling / Dry
$ Wall Mounted Type
$ Floor standing Type
$ Floor/Ceiling suspended Type
$ Duct Connected Type
Heating
$ Wall Mounted Type
$ Floor standing Type
$ Floor/Ceiling suspended Type
$ Duct Connected Type
B
A
OFF
OFF
ON
ON
C
Room temperature - setpoint
(R4668)
Cooling : – 0.5°C
Dry : – 0.5°C
Cooling : – 2.0°C
Dry : – 2.5~– 2.0°C
B
B
A
A
OFF
OFF
ON
ON
C
C
– 1.5°C
Room temperature - setpoint
(R6032)
Cooling : – 1.0°C
Dry : – 1.0°C
Cooling : – 2.0°C
Dry : – 2.5~– 2.0°C
B
A
OFF
ON
C
1.5˚C
Room temperature - setpoint
0˚C
(R4669)
B
A
OFF
ON
C
1.5˚C
1.0˚C
Room temperature - setpoint
0.5˚C
(R6033)