5 | Preparation
Installer reference guide
21
FTXP50~71M2V1B + FTXF20~71A2V1B + ATXF50~71A2V1B
Daikin room air conditioner
4P513661-8H – 2019.12
Class L1 liquid piping L1 gas piping
20~35 Ø6.4 Ø9.5
50~71 Ø6.4 Ø12.7
Refrigerant piping material
Piping material: Phosphoric acid deoxidised seamless copper.
Flare connections: Only use annealed material.
Piping temper grade and thickness:
Outer diameter (Ø) Temper grade Thickness (t)
(a)
6.4mm (1/4") Annealed (O) ≥0.8mm
t
Ø
9.5mm (3/8")
12.7mm (1/2")
(a)
Depending on the applicable legislation and the unit's maximum working pressure
(see "PS High" on the unit name plate), larger piping thickness might be required.
5.3.2 Refrigerant piping insulation
Use polyethylene foam as insulation material:
- with a heat transfer rate between 0.041 and 0.052 W/mK (0.035 and
0.045kcal/mh°C)
- with a heat resistance of at least 120°C
Insulation thickness
Pipe outer diameter (Ø
p
) Insulation inner diameter
i
)
Insulation thickness (t)
6.4mm (1/4") 8~10mm ≥10mm
9.5mm (3/8") 12~15mm ≥13mm
12.7mm (1/2") 14~16mm ≥13mm
i
i
p
p
If the temperature is higher than 30°C and the humidity is higher than RH80%, the
thickness of the insulation materials should be at least 20 mm to prevent
condensation on the surface of the insulation.
5.4 Preparing electrical wiring
5.4.1 About preparing electrical wiring
INFORMATION
Also read the precautions and requirements in the "General safety precautions"
chapter.