Electric Characteristics EDUS041820
30 Split Type Air Conditioners FTXR-T Series
10.Electric Characteristics
C: 3D120260
Unit Combination Power Supply Compressor OFM IFM
Indoor Unit Outdoor Unit Hz - Volts Voltage Range MCA MFA RLA W FLA W FLA
FTXR09TVJUW
FTXR09TVJUS
RX09RMVJU9
60 - 208
Max. 60 Hz 253 V
Min. 60 Hz 187 V
9.0 15 7.5 39 0.13 29 0.13
60 - 230
FTXR12TVJUW
FTXR12TVJUS
RX12RMVJU9
60 - 208
Max. 60 Hz 253 V
Min. 60 Hz 187 V
9.1 15 7.5 39 0.15 29 0.19
60 - 230
FTXR18TVJUW
FTXR18TVJUS
RX18RMVJU9
60 - 208
Max. 60 Hz 253 V
Min. 60 Hz 187 V
12.8 15 10.75 110 0.38 29 0.21
60 - 230
Symbols: Notes:
1. RLA is the max current that comes in cooling operation and heating
operation.
2. Maximum allowable voltage variation between phases is 2%.
3. Select wire size based on the larger value of MCA.
4. Instead of a fuse, use a circuit breaker.
5. Be sure to install a ground leak detector.
(This unit uses an inverter, which means that a ground leak detector
capable of handling high harmonics must be used in order to prevent
malfunctioning of the ground leak detector.)
MCA : Min. circuit amps (A)
MFA : Max. fuse amps (A)
RLA : Rated load amps (A)
OFM : Outdoor fan motor
IFM : Indoor fan motor
W : Fan motor rated output (W)
FLA : Full load amps (A)