Capacity Tables EDUS091128
24 Split Type Air Conditioners FTXS-L / FDXS-L Series
3D074636
Symbols: Note:
AFR : Airflow rate (m
3
/min.) 1. Ratings shown are net capacities which include a deduction for indoor fan
motor heat.
2. shows nominal (rated) capacities and power input.
3. TC, PI and SHC must be calculated by interpolation using the figures in the
above tables. (Figures out of the tables should not be used for calculation.)
4. SHC values not included in the table must be calculated using interpolation
with values of direct proportion.
5. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 25 ft
Level difference : 0 ft
6. Airflow rate (AFR) and Bypass factor (BF) are tabulated above table.
7. Cooling capacity at –15°C / 5°F
BF : Bypass factor
EWB : Entering wet bulb temp. (°C) / (°F)
EDB : Entering dry bulb temp. (°C) / (°F)
TC : Total capacity (kW) / (kBtu/h)
SHC : Sensible heat capacity (kW) / (kBtu/h)
PI : Power input (kW)
Temp: Celsius
TC, SHC, PI: kW
60 Hz, 208 - 230 V
INDOOR OUTDOOR
EWB EDB –15 (°CDB)
°C °C TC SHC PI
14.0 20.0 3.54 2.66 0.23
Temp: Fahrenheit
TC, SHC: kBtu/h
PI: kW
60 Hz, 208 - 230 V
INDOOR OUTDOOR
EWB EDB 5 (°FDB)
°F °F TC SHC PI
57.2 68.0 12.08 9.08 0.23