6 English
Preparation before Installation
•Attachment methods of metal plate electrical wiring cover
Attachthemetalplateelectricalwiringcoverasshownbelow.
1)Leanthemetalplateelectricalwiringcoverasshowninthegureandattachtab(1)onthelowersidetotheelectrical
wiringbox.
2)Attachtab(2)onthelowersideofthemetalplateelectricalwiringcover.
Tab (1)
Tab (2)
Tab (1)
3)Pushintheupperpartofthemetalplateelectricalwiringcoverandattachthe3tabs.
Ta b
CAUTION
Make sure that the shaded part ( ) will
not go inside the electrical wiring box.
Refrigerant Piping Work
With a multi indoor unit
, install as described in the installation manual supplied with the Multi outdoor unit.
1. Flaring the pipe end
1)Cutthepipeendwithapipecutter.
2)Removeburrswiththecutsurfacefacingdownward
sothatthechipsdonotenterthepipe.
3)Putthearenutonthepipe.
4)Flarethepipe.
5)Checkthatthearingisproperlymade.
Set exactly at the position shown below.
A
Flaring
Die
A
0-0.020 inch (0-0.5mm)
Clutch-type
Flare tool for R410A
0.039-0.059 inch (1.0-1.5mm)
Clutch-type (Rigid-type)
0.059-0.079 inch (1.5-2.0mm)
Wing-nut type (Imperial-type)
Conventional flare tool
(Cut exactly at
right angles.)
Remove burrs.
Check
Flare’s inner surface
must be flaw-free.
The pipe end must
be evenly flared in a
perfect circle.
Make sure that the
flare nut is fitted.
WARNING
•Donotusemineraloilonaredpart.
•Preventmineraloilfromgettingintothesystemasthiswouldreducethelifetimeoftheunits.
•Neverusepipingwhichhasbeenusedforpreviousinstallations.Onlyusepartswhicharedeliveredwiththeunit.
•NeverinstalladriertothisR410Aunitinordertoguaranteeitslifetime.
•Thedryingmaterialmaydissolveanddamagethesystem.
•Incompletearingmaycauserefrigerantgasleakage.
01_EN_3P297301-1.indd 6 10/20/2011 2:38:27 PM

Related product manuals