3-2. Left-side, left-back, or left bottom piping.
1) Attach the drain hose to the underside of the refrigerant pipes
with adhesive vinyl tape.
2) Be sure to connect the drain hose to the drain port in place of a
drain plug.
3) Shape the refrigerant pipe along
the pipe path marking on the
mounting plate.
4) Pass drain hose and refrigerant
pipes through the wall hole, then
set the indoor unit on mounting
plate hooks, using the mark-
ings at the top of indoor unit as a
guide.
5) Pull in the interconnecting wires.
6) Connect the inter-unit piping.
7) Wrap the refrigerant pipes and
drain hose together with insulation tape as right figure, in case of setting
the drain hose through the back of the indoor unit.
8) While exercising care so that the interconnecting wires do not catch indoor
unit, press the bottom edge of indoor unit with both hands until it is firmly
caught by the mounting plate hooks. Secure indoor unit to the mounting
plate with screws (M4 × 12L).
3-3. Wall embedded piping.
Follow the instructions given under
1) Insert the drain hose to this depth so it won’t be pulled out of the drain
pipe.
Left-side, left-back, or left bottom piping
       
 
 
  
 
 




How to set drain plug.
No gap.
Insert a hexagon wrench (4mm).
Do not apply lubricating
oil (refrigeration oil)
when inserting.
Application of causes
deterioration and drain
leakage of the plug.
Wrap insulating tape around the bent portion
of refrigerant pipe.
Overlap at least half the width of the tape
with each turn.
Drain
hose
Caulk this hole
with putty or
caulking material.
Bind with plastic
tape.
A
Mounting plate


 
 

×
  


Inner wall
Vinyl chloride
drain pipe
(VP-30)
Drain hose50mm
or more
Insert drain hose
to this depth so
it wont be pulled
out of drain pipe.
Outer wall
01_EN_3P207052-1.fm Page 8 Wednesday, September 19, 2007 4:46 PM