EasyManua.ls Logo

Daikin FTXS20K3V1B - Outdoor Fan System Check; Main Circuit Short Check

Daikin FTXS20K3V1B
131 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Check SiBE041134EB
102 Service Diagnosis
5.11 Outdoor Fan System Check
Check No.19 DC motor
5.12 Main Circuit Short Check
Check No.20 Check to make sure that the voltage between (+) and (–) of the diode bridge (DB1) is about 0 V
before checking.
Measure the resistance between the pins of the DB1 referring to the table below.
If the resistance is
or less than 1 k, short circuit occurs on the main circuit.
RXS20/25K2V1B, RXS20/25K3V1B, RXS20/25L2V1B, ARXS25L2V1B
(R21195)
YES
NO
NO
YES
Outdoor fan system is functioning.
Check the outdoor fan system.
Reconnect the connector.
Is the
outdoor fan running?
Fan motor
lead wire connector
disconnected?
Go to Check No. 16.
Positive terminal (+) of
digital multimeter
~
(2, 3)
+
(4)
~
(2, 3)
(1)
Negative terminal (–) of
digital multimeter
+
(4)
~
(2, 3)
(1)
~
(2, 3)
Resistance is OK. several k~ several M
Resistance is NG. 0 or
(R20802)
Multimeter
–~~+
1
2
3
4
+

Table of Contents

Other manuals for Daikin FTXS20K3V1B

Related product manuals