SiBE041134EB Field Settings
Trial Operation and Field Settings 109
4. Field Settings
4.1 Model Type Setting
ARC466A6
This remote controller is common to the heat pump model and cooling only model. Use the
DIP switch on the remote controller to set the heat pump model.
Set the DIP switch to H/P as shown in the illustration. (The factory set is the heat pump
side.)
4.2 When 2 Units are installed in 1 Room
Outline When 2 indoor units are installed in 1 room, 1 of the 2 indoor units and the corresponding
wireless remote controller can be set for different addresses.
Both the indoor unit PCB and the wireless remote controller need alteration.
Indoor Unit PCB
Cut the address setting jumper JA on the control PCB.
Caution Replace the PCB if you accidentally cut a wrong jumper.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of
them.
Wireless Remote
Controller
Cut the address setting jumper.
H/P C/O
DIP switch
(R18257)
JA
JC
JB
ADDRESS
1
2
JA
EXIST
CUT
(R18258)
1
2
Address
Jumper
(R14631)
EXIST
CUT