SiENBE04-401A Outdoor Unit / RK(X)H-C, ARK(X)H-C, R(Y)N-C
Removal Procedure 215
Confirm that the
refrigerant is completely
empty in the refrigerant
circuit before starting
work.
Warning
Since it may happen that
refrigeration oil in the
compressor will catch fire,
prepare wet cloth so as to
extinguish the fire quickly.
Warning
Ventilate when the refrigerant
leaks during the work. (If the
refrigerant is exposed to the
fire, it will cause toxic gas).
Caution
Be careful about pipes and so
on, which were heated up by a
gas brazing machine, so as
not to get burnt on your
hands.
Pay attention so that the fins
of the heat exchanger will
not be burnt.
Be sure to apply
nitrogen’s replacement
when heating up the
brazing part.
3
Remove the brazing
part on the discharge
side of the compressor.
4
Heat up the brazing
part on the suction side
of the compressor and
then remove it.
5
Lift the compressor and
remove it.
Step Procedure Points
(R4080)
(R4081)

Table of Contents