Outdoor Unit / RK(X)H-C, ARK(X)H-C, R(Y)N-C SiENBE04-401A
190 Removal Procedure
3. Outdoor Unit / RK(X)H-C, ARK(X)H-C, R(Y)N-C
3.1 Removal of External Panels
Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Step Procedure Points
1
The stop valve cover
can be removed when
the fixing screw is
removed.
As hooks are provided, slide
the cover downward to
remove.
The forced cooling operation
in the pumping down mode
can be carried out by
pushing the ON / OFF button
on the indoor unit for 5
seconds.
Stop valve
cover
(R4026)
Stop valve
(liquid)
Stop valve (gas)