EasyManuals Logo

Daikin FUY71FJV1 User Manual

Daikin FUY71FJV1
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #101 background imageLoading...
Page #101 background image
Si20-701_B Troubleshooting by Remote Controller
94
Remote Controller Display
A6
Applicable Models
FDQ200 • 250
Method of Error Detection
Detect the status in which the separate power supply for
the fan is cut OFF.
Error Decision Conditions
Unable to detect that separate power supply for the
indoor unit fan is turned ON
Supposed Causes
îš„ Defective power supply for the indoor unit fan motor
îš„ Clogging in the drain pipe
îš„ Protection device for the indoor unit fan is operated.
îš„ Defective contact for the fan wiring circuit

Table of Contents

Other manuals for Daikin FUY71FJV1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FUY71FJV1 and is the answer not in the manual?

Daikin FUY71FJV1 Specifications

General IconGeneral
BrandDaikin
ModelFUY71FJV1
CategoryAir Conditioner
LanguageEnglish

Related product manuals