EasyManuals Logo

Daikin FUY71FJV1 User Manual

Daikin FUY71FJV1
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #266 background imageLoading...
Page #266 background image
Troubleshooting by Remote Controller Si20-701_B
259
3.55
JC
Suction Pipe Pressure
Sensor Abnormality
Remote Controller Display
JC
Applicable Models
RZQ(S)-B, RZQ-C7, CMSQ
Method of Error Detection
The error is detected from pressure detected by low
pressure sensor.
Error Decision Conditions
When the suction pipe pressure sensor is short circuit or
open circuit.
Supposed Causes
îš„ Defective low pressure sensor system
îš„ Connection of high pressure sensor with wrong
connection.
îš„ Defective outdoor unit PCB.

Table of Contents

Other manuals for Daikin FUY71FJV1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FUY71FJV1 and is the answer not in the manual?

Daikin FUY71FJV1 Specifications

General IconGeneral
BrandDaikin
ModelFUY71FJV1
CategoryAir Conditioner
LanguageEnglish

Related product manuals