Troubleshooting by Remote Controller Si20-701_B
477
Check for Clogged Points
Temperature differences must occur before or after the
clogged points!
Check points
Check
factor
Causes Remedies
(1)
Around
expansion
mechanism
Temperature
difference
· Dust
· Choked moisture
· Reduced effective pipe
diameter due to adherent
contamination, etc.
Replace the electronic
expansion valve.
(2)
Accumulator
Frosting · Choked moisture Blow a nitrogen gas, and
then replace the
refrigerant.
(3)
Distributor
Temperature
difference
· Dust
· Choked moisture
· Reduced effective pipe
diameter due to adherent
contamination, etc.
Replace the heat
exchanger or distributor.
(4) Field
piping
Temperature
difference
· Collapsed pipe Replace the pipe.
(5) Stop
valve
Temperature
difference
· The stop valve is not fully
open.
Open the stop valve fully.
CHECK 11
ACC
Indoor Unit
(3)
(4)
(2)
(5)
(1)
(3)
Outdoor Unit
COMP.

Table of Contents

Other manuals for Daikin FUY71FJV1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FUY71FJV1 and is the answer not in the manual?

Daikin FUY71FJV1 Specifications

General IconGeneral
BrandDaikin
ModelFUY71FJV1
CategoryAir Conditioner
LanguageEnglish

Related product manuals