Troubleshooting by Remote Controller Si20-701_B
329
3.75
P1
Open Phase or Power
Supply Voltage Imbalance
Remote Controller Display
P1
Applicable Models
RZQ-K/H, RZQ(S)-B/C, RZQG, RZR-KU/HU
Method of Error Detection
The error is detected according to the voltage waveform
of main circuit capacitor built in inverter.
Error Decision Conditions
When the aforementioned voltage waveform becomes
identical with the waveform of the power supply open
phase.
Supposed Causes
îš„ Open phase
îš„ Voltage imbalance between phases
îš„ Defective outdoor inverter PCB
• Defective main circuit capacitor
• Power unit (Disconnection in diode module)
• Defective magnetic relay
• Improper main circuit wiring



