Si20-701_B Troubleshooting by Remote Controller
450
3.107
UF
Transmission Error
between Indoor and Outdoor
Unit / Piping and Wiring
Mismatch / Refrigerant
Shortage
Remote Controller Display
UF
Applicable Models
RZQ-K/H, RZR-KU/HU, RZQG
Method of Error Detection
Check the transmission between the indoor and outdoor
units with a micro-computer when the power turned ON.
Detect by checking the following temperature differences
during compressor operation.
A: Difference in temperature detected by the indoor
heat exchanger thermistor and the indoor suction
air thermistor
B: Difference in indoor suction air thermistor
evaporation temperature (Te) (or condensing
temperature (Tc) during heating operation) detected
by the indoor heat exchanger thermistor and the
compressor sensor
Error Decision Conditions
When the transmission wiring between the indoor and
outdoor units is incorrect
When the following conditions continue for 20 minutes
during compressor operation
A: indoor heat exchanger thermistor – indoor suction
air thermistor < 4ºC, and
B: indoor heat exchanger thermistor – Te (or Tc during
heating operation) > 14ºC (24ºC during heating
operation)

Table of Contents

Other manuals for Daikin FUY71FJV1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FUY71FJV1 and is the answer not in the manual?

Daikin FUY71FJV1 Specifications

General IconGeneral
BrandDaikin
ModelFUY71FJV1
CategoryAir Conditioner
LanguageEnglish

Related product manuals