EasyManuals Logo

Daikin FUY71FJV1 User Manual

Daikin FUY71FJV1
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #135 background imageLoading...
Page #135 background image
Si20-701_B Troubleshooting by Remote Controller
128
3.20
CJ
Remote Controller
Thermistor Abnormality
Remote Controller Display
CJ
Applicable Models
FHY, FHYC, FUY, FAY, FV(Y) (Available for 2 remote
controller use.), FHC, FH, FDBG, FDBT, FDMG, FCQ(H),
FMCQ, FFQ, FHQ, FAQ, FBQ, FDQ, FMDQ, FUQ, FVQ,
FCQG, FHQG
Method of Error Detection
Even if remote controller thermistor is defective, system
is possible to operate by system thermistor.
The error is detected by temperature of remote controller
thermistor.
Error Decision Conditions
The error is generated when the remote controller
thermistor becomes disconnected or shorted when the
unit is running.
Even if the remote controller thermistor is defective, the
system can operate with the system thermistor.
Supposed Causes
îš„ Defective thermistor
îš„ Broken wire